Permit: T07CM00883

Parcel: 11941288A


Addresses:

1451 W AJO WY

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
USE 2 SEPARATE CIRCUIT BREAKERS AT OFFICE PANEL OR USE TWO NEUTRALS WHEN USING TWIN BREAKER FOR 2 CKTS.
OK TO CLEAR PEDESTAL FOR GATE
05/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS NEED TO BE 6' MIN. APART FOR NEC
2. SUPPORT #4 BARE & 3/4" PVC AT PEDESTAL
3. INSTALL ADDRESS LABEL ON PEDESTAL
4. SUPPORT J-BOXES (6X6) & GROUND
5. SUPPORT 3/4" PVC AT SERVICE PANEL BY OFFICE AND I.D CIRCUIT BREAKER

PLANS NOT IN OFFICE