Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM00883
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* USE 2 SEPARATE CIRCUIT BREAKERS AT OFFICE PANEL OR USE TWO NEUTRALS WHEN USING TWIN BREAKER FOR 2 CKTS. OK TO CLEAR PEDESTAL FOR GATE |
|
05/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS NEED TO BE 6' MIN. APART FOR NEC 2. SUPPORT #4 BARE & 3/4" PVC AT PEDESTAL 3. INSTALL ADDRESS LABEL ON PEDESTAL 4. SUPPORT J-BOXES (6X6) & GROUND 5. SUPPORT 3/4" PVC AT SERVICE PANEL BY OFFICE AND I.D CIRCUIT BREAKER PLANS NOT IN OFFICE |