Case: T06FR02555

Parcel: 138041810


Addresses:

6500 S 12TH AV

Inspection Status: Violation

Inspection History: VIOL - MOTOR FUEL DISPENSING

Date Description Inspector Results Comments
09/11/2006 VIOL - MOTOR FUEL DISPENSING Violation IFC 2203.2- An emergency disconnect switch shall be located within 100' but not less than 20' from fuel dispensers.
*Dispenser #5,6 shall be removed or emergency disconnects shall be relocated. Permits are required for work.
09/11/2006 VIOL - MOTOR FUEL DISPENSING Violation IFC 2203.2- Emergency disconnect switches shall be readily identified by a sign stating "EMERGENCY FUEL SHUTOFF".
09/11/2006 VIOL - MOTOR FUEL DISPENSING Violation IFC 2204.2.4- Dispensing devises shall be in clear view of the attendant at all times.
*Dispenser #5,6 is completely blocked from view by other equipment.
09/11/2006 VIOL - MOTOR FUEL DISPENSING Violation IFC 2205.2.2- Automatic-closing emergency shutoff valves shall be checked not less than once per year by manually tripping the hold-open linkage. Show proof.
09/11/2006 VIOL - MOTOR FUEL DISPENSING Violation IFC 2205.2- Motor fuel dispensing equipment shall be maintained in proper working order at all times.
*Dispenser #2 (89 octane) hose is leaking and shall be repaired.
09/11/2006 VIOL - MOTOR FUEL DISPENSING Violation IFC 2203.1- Dispensing devices shall be located as follows:
#4- Such that the nozzle, when the hose is fully extended, will not reach within 5' of building openings.