Inspection Status: Violation
Inspection History: VIOL - MOTOR FUEL DISPENSING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | IFC 2203.2- An emergency disconnect switch shall be located within 100' but not less than 20' from fuel dispensers. *Dispenser #5,6 shall be removed or emergency disconnects shall be relocated. Permits are required for work. |
|
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | IFC 2203.2- Emergency disconnect switches shall be readily identified by a sign stating "EMERGENCY FUEL SHUTOFF". | |
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | IFC 2204.2.4- Dispensing devises shall be in clear view of the attendant at all times. *Dispenser #5,6 is completely blocked from view by other equipment. |
|
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | IFC 2205.2.2- Automatic-closing emergency shutoff valves shall be checked not less than once per year by manually tripping the hold-open linkage. Show proof. | |
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | IFC 2205.2- Motor fuel dispensing equipment shall be maintained in proper working order at all times. *Dispenser #2 (89 octane) hose is leaking and shall be repaired. |
|
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | Violation | IFC 2203.1- Dispensing devices shall be located as follows: #4- Such that the nozzle, when the hose is fully extended, will not reach within 5' of building openings. |