Case: T06FR02555
Case Details
Entered Date:
09/11/2006
Applicant:
GIANT INDUSTRIES ARIZONA INC
Description:
Motor Fuel Dispensing Inspection
Outstanding Inspections
Case Number: T06FR02555
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2006 | INSP - FULL | JLANGEJA | Correction Required | This complaint was justified and a full inspection was performed. |
| 09/11/2006 | VIOL - ADMINISTRATION | JLANGEJA | Violation | IFC 110.1.1- Unsafe Condition. Dispensers #5,6 and #7,8 have been Red Tagged and shall remain out of service until the unsafe condition can be remedied. Call 791-4502 when the condition has been fixed. |
| 09/11/2006 | VIOL - FIRE SERVICE FEATURES | JLANGEJA | Violation | IFC 505.1- Address numbers shall be in accordance with Pima County address display requirements. See handout. |
| 09/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | IFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. 1. electrical panels (2) on W wall in storage room. 2. emergency disconnect to compressor. |
| 09/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | IFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. junction box on light pole shall be covered (NW corner). 2. light fixture shall be secured (storage room). 3. receptacle to soda machines needs cover (E of booth). |
| 09/11/2006 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | IFC 703.1- Fire resistive-rated construction shall be maintained. *Sheetrock shall be repaired in ceiling of storage room. *Openings to roof structure shall be closed around fans. |
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2203.1- Dispensing devices shall be located as follows: #4- Such that the nozzle, when the hose is fully extended, will not reach within 5' of building openings. |
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2203.2- An emergency disconnect switch shall be located within 100' but not less than 20' from fuel dispensers. *Dispenser #5,6 shall be removed or emergency disconnects shall be relocated. Permits are required for work. |
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2203.2- Emergency disconnect switches shall be readily identified by a sign stating "EMERGENCY FUEL SHUTOFF". |
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2204.2.4- Dispensing devises shall be in clear view of the attendant at all times. *Dispenser #5,6 is completely blocked from view by other equipment. |
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2205.2- Motor fuel dispensing equipment shall be maintained in proper working order at all times. *Dispenser #2 (89 octane) hose is leaking and shall be repaired. |
| 09/11/2006 | VIOL - MOTOR FUEL DISPENSING | JLANGEJA | Violation | IFC 2205.2.2- Automatic-closing emergency shutoff valves shall be checked not less than once per year by manually tripping the hold-open linkage. Show proof. |
Completed Inspections
Case Status: COMPLETE
Case Number: T06FR02555
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/16/2006 | INSP - REINSPECTION | JLANGEJA | Approved | dispensers inspected, #5/6 needs float chains attached to emergency shut-off linkage before it can be placed back in service, Eddie (975-1191) will order sensor for dispenser pan, #7/8 is ready for service immediately |