Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
09/11/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.6- Open junction boxes and open wiring splices shall be prohibited.
1. junction box on light pole shall be covered (NW corner).
2. light fixture shall be secured (storage room).
3. receptacle to soda machines needs cover (E of booth).
09/11/2006 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment.
1. electrical panels (2) on W wall in storage room.
2. emergency disconnect to compressor.