Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. junction box on light pole shall be covered (NW corner). 2. light fixture shall be secured (storage room). 3. receptacle to soda machines needs cover (E of booth). |
|
| 09/11/2006 | VIOL - BUILDING SVCS & SYSTEMS | Violation | IFC 605.3- A working space of not less than 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. 1. electrical panels (2) on W wall in storage room. 2. emergency disconnect to compressor. |