Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2006 | ELECTRIC - FINAL | Approved | ||
| 11/16/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* A MEETING WAS HELD WITH J.JAWORSKY, THE GENERAL CONTRACTOR AND MYSELF THERE WAS NO INSTRUCTIONS ON SITE. THE UL WHITE BOOK FOR RECESSED LUMINARIES WAS REFERENCED. HAVE THE PLANS EXAMINER REVIEW A PLAN FOR INSTALLING FIXTURES. |
|
| 11/15/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. WAITING ON MANUFACTURES LISTING FOR FIXTURES. |
|
| 11/09/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE PROVIDE MFR. INSTRUCTIONS FOR 2X4 LAY IN FIXTURES FOR USE WITHOUT GRID. 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 -- DEVICES & LIGHTS. 3. WE HAVE EXPOSED CONDUCTORS. 4. INSTA-HOT NOT CORD & PLUG LISTED ALSO, VERIFY CIRCUIT AND LOADS. 5. PROVIDE SUPPORT FOR NEW A/C DISCONNECT. 6. WHERE ARE MAINTENANCE SERVICE RECEPTACLE AS PER PLANS AND 210.63 |