Permit: T06CM01707

Parcel: 12709011P

Inspection Status: Approved

Inspection History: ELECTRIC - CONSTRUCTION POWER

Date Description Inspector Results Comments
10/26/2006 ELECTRIC - CONSTRUCTION POWER Approved OK DISCONNECTS & LABELING

1. INSTALL ALL FUSES
10/25/2006 ELECTRIC - CONSTRUCTION POWER Approved IVRS - Inspection :*
2ND INSPECTION
OK TO CLEAR TEC #1 #2

NEED TO RE- LABEL MAIN DISCONNECTS, THEY CANNOT ALL BE THE SAME. THEY CAN BE 1-2-3 ASIDE FROM 154,
THE PANELS ALSO HAVE TO BE LABELED SAME AS METER OR SERVICE DISCONNECT.
10/04/2006 ELECTRIC - CONSTRUCTION POWER Not ready for Inspection IVRS - Inspection :*
1. SUPPORT CONDUITS & SE CABLE ABOVE PANEL
2. PROTECT M/C AT SHALLOW STUDS
3. SUPPORT M/C UPON EXITING WALLS

OK STUD FRAME WALLS