Permit: T06CM01707

Parcel: 12709011P

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01707

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/01/2006 FRAMING Approved IVRS - Inspection :*
RECEIVED LETTER FROM ARCHITECT STATING THE APPROVED CHANGE IN STUD MATERIAL FROM 20 GA METAL TO WOOD.
10/23/2006 FRAMING Partial Approval IVRS - Inspection :*
1. NEED RFI FROM ARCHITECT STATING THAT THE USE OF WOOD STUDS IN PLACE OF 20 GA. STD. IS ACCEPTABLE.
2. NEED TO FRAME BATHROOM CEILINGS FOR HARD CEILINGS
DROP CEILINGS IN RESTROOMS IS AGAINST CODE.
3. OK TO SHEETROCK PROGRESS AREAS.