Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - HAZARDOUS MATERIALS,GEN
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Approved | TFC 2703.8.7.2- Cabinets shall be clearly identified in an approved manner with red letters on a contrasting background stating "HAZARDOUS-KEEP FIRE AWAY". | |
| 04/28/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Approved | TFC 2703.5.1- Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. 1. 55 gallon drums (waste oil) 2. fuel containers 3. 5 gallon buckets |
|
| 04/28/2005 | VIOL - HAZARDOUS MATERIALS,GEN | Approved | TFC 2703.3.1- Hazardous materials shall not be released into a sewer, storm drain,...onto the ground or into the atmosphere. The person responsible for an unauthorized discharge shall institute and complete all actions necessary to remedy the effects of such discharge. Engine washing operations which release hazardous materials onto the ground shall cease immediately and an alternate method shall be approved. (South end of property) |