Case Number: T05FR00586
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
04/28/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.1- Identified electrical hazards shall be abated. 1. light fixture by electrical panel 2. hose bib below electrical panel shall not allow standing water. 3. GFI protected electrical circuits are required within 6 feet of standing water. 4. electrical panel missing blanks. (East wall) 5. shop light needs grounded switch or remove. 6. upstairs wiring to lights shall be protected.
04/28/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working spaceof not less than 30" x 36" x 78" shall be provided...electrical service equipment. 1. North wall panels 2. East wall disconnect 3. East wall outside
04/28/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. coffee pot 2. North wall panel to upstairs
04/28/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually.
04/28/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.7- Fire extinguishers shall be installed on their hanger or bracket. See handout.
04/28/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 906.9- Height above floor.
04/28/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1008.1.8- Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
04/28/2005 VIOL - COMPRESSED GASES JLANGEJA Violation TFC 3003.3- Compressed gas cylinders shall be secured to prevent accidental dislodgement. (several throughout)

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00586
Case Description: INSPECTION
Total Completed Inspections - 5
End Date Description Inspector Results Comments
04/28/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Approved TFC 2703.3.1- Hazardous materials shall not be released into a sewer, storm drain,...onto the ground or into the atmosphere. The person responsible for an unauthorized discharge shall institute and complete all actions necessary to remedy the effects of such discharge. Engine washing operations which release hazardous materials onto the ground shall cease immediately and an alternate method shall be approved. (South end of property)
04/28/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Approved TFC 2703.5.1- Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. 1. 55 gallon drums (waste oil) 2. fuel containers 3. 5 gallon buckets
04/28/2005 VIOL - HAZARDOUS MATERIALS,GEN JLANGEJA Approved TFC 2703.8.7.2- Cabinets shall be clearly identified in an approved manner with red letters on a contrasting background stating "HAZARDOUS-KEEP FIRE AWAY".
04/28/2005 VIOL - WELDING & OTHER HOT WRK JLANGEJA Approved TFC 2604.1- Protection of combustibles shall be in accordance with NFPA standards. A minimum of 35' shall be provided or a fire resistive curtain shall be used.
04/28/2005 VIOL - FIRE SERVICE FEATURES JLANGEJA Approved TFC 504.2- Exterior doors that have been blocked shall be marked appropriately.