Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Identified electrical hazards shall be abated. 1. light fixture by electrical panel 2. hose bib below electrical panel shall not allow standing water. 3. GFI protected electrical circuits are required within 6 feet of standing water. 4. electrical panel missing blanks. (East wall) 5. shop light needs grounded switch or remove. 6. upstairs wiring to lights shall be protected. |
|
| 04/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working spaceof not less than 30" x 36" x 78" shall be provided...electrical service equipment. 1. North wall panels 2. East wall disconnect 3. East wall outside |
|
| 04/28/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. coffee pot 2. North wall panel to upstairs |