Permit: T00CM03120

Parcel: 128010010

Inspection Status: Denied

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/24/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0999*
TRAC LIGHTING NEEDS SIESMIC SUPPORT
J-BOXES OVERFILLED (SEE ART 370-6)
CONDUIT AND J-BOXES CANNOT BE SECURED FROM THE GRID STRUCTURAL INSTALL SEPERATE SIESMIC WIRE FOR ELEC SUPPORT
FINISH ALL MAKE UP OF J-BOXES WIRE STILL BEING PULLED ALONG WITH CONDUIT INSTALLATION
SECURE ALL EMT WITHIN 3" OF J-BOXES (PER 248-13 N.E.C.
FIELD COLLECTED AFTER HRS INSPECTION 98.50 FROM JOSEPH CLONTAN CHECK # 4719