Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2000 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection 0999* TRAC LIGHTING NEEDS SIESMIC SUPPORT J-BOXES OVERFILLED (SEE ART 370-6) CONDUIT AND J-BOXES CANNOT BE SECURED FROM THE GRID STRUCTURAL INSTALL SEPERATE SIESMIC WIRE FOR ELEC SUPPORT FINISH ALL MAKE UP OF J-BOXES WIRE STILL BEING PULLED ALONG WITH CONDUIT INSTALLATION SECURE ALL EMT WITHIN 3" OF J-BOXES (PER 248-13 N.E.C. FIELD COLLECTED AFTER HRS INSPECTION 98.50 FROM JOSEPH CLONTAN CHECK # 4719 |