Permit Details

Status:
Final
Type:
COMMERCIAL ALTERATION
Apply Date:
06/22/2000
Applicant:
SONORA EXPEDITING
Description:
TI:RETAIL
Architects:
  • BLACK, MICHAEL RAY
Contractors:
  • DAN KUYKENDALL ENTERPRISES INC

Permit Reviews

Permit Number - T00CM03120
Permit Status: Final
Permit Description: TI:RETAIL
Start Date Submittal Complete Date Status  
07/31/2000 REVISION - RESUBMITTAL 08/02/2000 COMPLETED Review Details
08/07/2000 REVISION - RESUBMITTAL 08/16/2000 COMPLETED Review Details

Completed Inspections

Permit Status: Final
Permit Number: T00CM03120
Permit Description: TI:RETAIL
Total Completed Inspections - 1
Date Description Inspector Results Comments
08/24/2000 ELECTRIC - ABOVE CEILING RSUBA Approved IVRS - Inspection 0999*
TRAC LIGHTING NEEDS SIESMIC SUPPORT
J-BOXES OVERFILLED (SEE ART 370-6)
CONDUIT AND J-BOXES CANNOT BE SECURED FROM THE GRID STRUCTURAL INSTALL SEPERATE SIESMIC WIRE FOR ELEC SUPPORT
FINISH ALL MAKE UP OF J-BOXES WIRE STILL BEING PULLED ALONG WITH CONDUIT INSTALLATION
SECURE ALL EMT WITHIN 3" OF J-BOXES (PER 248-13 N.E.C.
FIELD COLLECTED AFTER HRS INSPECTION 98.50 FROM JOSEPH CLONTAN CHECK # 4719