Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00CM02406
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2001 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
02/20/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* 1) LABEL UNITS PERMANENTLY NO INK! 2) FINISH INSULATING COPPER FROM STEEL UNISTRUT 3) MOVE SEWER VENT TO 3' ABOVE OR 10' AWAY FROM OUTSIDE AIR INTAKE | |
02/05/2001 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* CONCEAL CONTROL WIRING SMALL CONDENSERS SECURE IN PLACE CLOSE DIRECTION OF CONDENSER AIR DISCHARGE DUMPING INTO ADJ CONDENSERS ISOLATE ALL COPPER FROM CHECK FOOT PRINTS BY MANUF. FOR PROPER |