Case Details

Status:

COMPLIAN

Type:

RES: MINIMUM HOUSING

Entered Date:

06/21/2017

Applicant:

FLORES CATHERINE ALICIA

Description:

air conditoner isnt working and having electical issues

Outstanding Inspections

Case Number: T17DV02645
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 11
End Date Description Inspector Results Comments
10/03/2017 EMERGENCY CALL OUT VIDAL Item closed
10/03/2017 NPO(EL)-MAIN/PANEL/SUB/DISCONT VIDAL Item closed
10/03/2017 NPO(EL)-WIRING/SWITCH/OUTLT/FX VIDAL Item closed
10/03/2017 NPO(PL)-WATER HEATERS VIDAL Item closed
10/03/2017 NPO(HC)-COOLING VIDAL Item closed
10/03/2017 NPO(HC)-HEATING & VENTILATION VIDAL Item closed
10/03/2017 NPO - SMOKE ALARMS VIDAL Item closed
10/03/2017 NPO - OTHER VIDAL Item closed
10/03/2017 NPO - EXT. BUILDING MAINTENANC VIDAL Item closed
10/03/2017 NPO - WORK WITHOUT PERMIT VIDAL Item closed
10/03/2017 NPO - INT. BUILDING MAINTENANC VIDAL Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T17DV02645
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 3
End Date Description Inspector Results Comments
06/21/2017 INSP - INITIAL CODE ENFORCMENT VIDAL Approved Received call from the office and the unit had no AC. Arrived and the tenants were on site and the AC package unit on roof is running and not cooling. The temp. from the vents was 76 degrees to 79 degrees, The outside temp. was at 113 degrees. Did go on the roof and the compressor appears to not be operating. The temp. air from the fan was not hot. The roof has been replaced and the penatration on the roof have not been sealed. The exterior doors are sealed, the window in the northwest bedroom is not sealed, the smoke detectors are not working properly, the light fixture in the northwest bedroom goes on and off, the rear porch is not anchored properly and needs to be removed and replace with a permit if going to replace the porch. Did call Rick Hollander to check the electrical system due to the tenants are stated power surges and the lights dimming. Did call the owner due to the temp. in the house and the tenant has kids and was reading temp. of 90 degrees to 93 degrees. The owner was going to place the tenant in a hotel for the night and the owner has people comming to check some of the items that need to be repaired. Did do the posting of Do Not Enter on the front window and the owner signed the paperwork. The owner or the tenant will call if the AC is repaired to let the tenant back into the house. The owner stated that her AC service man can't come until Friday or Saturday to check the unit. That's who installed the unit. RV.
06/21/2017 INSP - INITIAL CODE ENFORCMENT HOLLANDER Approved Inspector RV called me out due to electrical hazards. I found the open spaces or missing filler blanks in the panel dead front. The breakers were not properly labeled or correct manufactuer to the panel. The wires for the A/C unit were not correctly identified. The entrance into the panel was above current carring parts without the proper sealing device. The conduit was not properly supported. We tested the voltage for all circuits and they appeared within correct ranges. The Compressor on the A/C unit does not appear to be operating.
10/03/2017 INSP - FOLLOW UP CODE ENFORCE VIDAL Approved The permit T17CM05929 has been issued on 9-29-17 and the contractor will be calling the inspection in and should be there for the inspection. At this time the case will be closed. Violation Abated, Close Case. RV.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T17DV02645
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 2
Date Name
06/21/2017 NOTICE OF VIOLATION ISSUED
10/03/2017 VIOLATION CLOSED