Case Details

Status:

COMPLIAN

Type:

EMERGENCY
Address:

Entered Date:

12/06/2016

Applicant:

CHADWICK PAUL J SURVIVORS TR

Description:

Unsafe electrical service to the property main panel missing face plate

Case Violations

Case Number: T16DV08237
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Violations: 4
Violation Date Code Statue
12/22/2016 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
12/22/2016 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.
12/22/2016 T.C. Ch. 16, Sec. 16-11(a)(3) Every existing dwelling unit shall be provided with smoke detectors in good operating condition as required by the Tucson Fire Code of the City of Tucson.
12/22/2016 T.C. Ch. 16, Sec. 16-11(a)(2) Every dwelling unit or guest room shall have unobstructed access directly to the outside, or to a public corridor. Every door, stairway, passageway or other means of exit shall be of sufficient size, width and arrangement so as to provide safe and rapid egress in the event of fire. Every walking surface of any means of exit shall be maintained free of warping, rotting, or other damage or obstructions so as to provide safe and rapid egress in the event of fire.

Outstanding Inspections

Case Number: T16DV08237
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
12/28/2016 EMERGENCY CALL OUT VINDIOLA Follow-up inspection
12/28/2016 NPO(EL)-MAIN/PANEL/SUB/DISCONT VINDIOLA Follow-up inspection
12/28/2016 NPO(EL)-WIRING/SWITCH/OUTLT/FX VINDIOLA Follow-up inspection

Completed Inspections

Case Status: COMPLIAN
Case Number: T16DV08237
Case Description: EMERGENCY
Total Completed Inspections - 2
End Date Description Inspector Results Comments
12/06/2016 INSP - INITIAL CODE ENFORCMENT VINDIOLA Approved THERE ARE UNGROUND FEEDERS RUNNING FROM THE MAIN DISCONNECT LOCATED AT 832 E 7TH ST TO THE ADJACENT PROPERTY LOCATED AT 828 E 7TH ST. THESE FEEDERS ARE ENERGIZING A PANEL MOUNTED ON A WOOD POST AT 828 E 7TH ST. THERE ARE EXTENSION CORDS AND EXPOSED NONMETALLIC SHEATH CABLE ENERGIZING THE FIRE DAMAGED HOME WHICH WAS CONDEMNED IN 2011 AND THE DILAPIDATED SHED'S PANEL. THE SHED'S PANEL HAS UNDERGROUND ENERGIZED FEEDERS RUNNING TO THE REAR DUPLEXES DISCONNECT. THE MAIN DISCONNECT HAS A MISSING DEAD FRONT. LACK OF PROPER LABELING. RUNNING UNDERGROUND FEEDER TO ADJACENT PROPERTY. THE PANEL LOCATED AT THE GAZEBO HAS A JUNCTION BOX WITH AN RV RECEPTACLE POWERING AN OCCUPIED RV ON THE PROPERTY. THE MAIN DISCONNECT WAS ORDERED TO BE SHUT DOWN BY TEP DUE TO HAZARDOUS CONDITIONS, THE HOME WAS CONDEMNED FOR LACK OF POWER.
12/29/2016 INSP - FOLLOW UP CODE ENFORCE VINDIOLA Approved On-site inspections were conducted by DSD inspector, corrective action as followed: Install proper grounding bar and hardware to downstream panel Install smoke detectors in the interior of home, all bedrooms and hallways Water heater lacks discharge pipe from TPR valve per 2012 IRC DSD Inspector will return to inspect

Completed Activity Special Conditions

Case Description - EMERGENCY
Case Number - T16DV08237
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date Name
12/09/2016 CONTACTED BY PHONE
12/28/2016 CONTACTED IN PERSON
01/10/2017 CONTACTED BY EMAIL
08/02/2017 VIOLATION CLOSED
12/07/2016 REFERENCE