Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T16DV08237
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2016 | INSP - INITIAL CODE ENFORCMENT | Approved | THERE ARE UNGROUND FEEDERS RUNNING FROM THE MAIN DISCONNECT LOCATED AT 832 E 7TH ST TO THE ADJACENT PROPERTY LOCATED AT 828 E 7TH ST. THESE FEEDERS ARE ENERGIZING A PANEL MOUNTED ON A WOOD POST AT 828 E 7TH ST. THERE ARE EXTENSION CORDS AND EXPOSED NONMETALLIC SHEATH CABLE ENERGIZING THE FIRE DAMAGED HOME WHICH WAS CONDEMNED IN 2011 AND THE DILAPIDATED SHED'S PANEL. THE SHED'S PANEL HAS UNDERGROUND ENERGIZED FEEDERS RUNNING TO THE REAR DUPLEXES DISCONNECT. THE MAIN DISCONNECT HAS A MISSING DEAD FRONT. LACK OF PROPER LABELING. RUNNING UNDERGROUND FEEDER TO ADJACENT PROPERTY. THE PANEL LOCATED AT THE GAZEBO HAS A JUNCTION BOX WITH AN RV RECEPTACLE POWERING AN OCCUPIED RV ON THE PROPERTY. THE MAIN DISCONNECT WAS ORDERED TO BE SHUT DOWN BY TEP DUE TO HAZARDOUS CONDITIONS, THE HOME WAS CONDEMNED FOR LACK OF POWER. |