Case: T14DV02111
Case Details
Entered Date:
04/02/2014
Applicant:
PROPERTY MANAGEMENT CO: MICHAEL FUNKHOUSER
Description:
HAZARDOUS WIRING/ WORK WITHOUT PERMITS
Case Violations
Case Number: T14DV02111
Case Status: COMPLIAN
Case Description: WORK WITHOUT PERMITS-COMMERCL
Total Violations: 1
| Violation Date | Code Statue |
|---|---|
| 08/15/2014 | T.C. Ch. 16, Sec. 16-13(b) ACCUMULATION OF REFUSE PROHIBITED. Each owner, lessee, tenant, resident or occupant shall maintain a property so it is free of accumulated refuse and debris. Accumulated refuse and debris means contained or uncontained refuse and debris that is present on the property in a manner not authorized by the Tucson Code. Material recycling facilities meeting the requirements of section 15-24.7 are exempt from this prohibition. |
Outstanding Inspections
Case Number: T14DV02111
Case Status: COMPLIAN
Case Description: WORK WITHOUT PERMITS-COMMERCL
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/25/2016 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | VALDEZ | Extension granted | |
| 10/25/2016 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | VALDEZ | Extension granted | |
| 10/25/2016 | NPO - WORK WITHOUT PERMIT | VALDEZ | Extension granted |
Completed Inspections
Case Status: COMPLIAN
Case Number: T14DV02111
Case Description: WORK WITHOUT PERMITS-COMMERCL
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2014 | INSP - INITIAL CODE ENFORCMENT | VALDEZ | Approved | THERE ARE DILAPIDATED SUPPORT POSTS THOUGH OUT THE PARK WHICH HAVE FAILED IN SUPPORTING THE OVERHEAD FEEDERS WHICH ARE CURRENTLY RESTING AND CONTACTING THE EXTERIOR BODY OF THE MOBILES HOMES. THERE ARE NEWLY INSTALL FEEDERS TO MULITPLE UNMARKED LOCATIONS. ALL THIS WORK WAS DONE WITH OUT A PERMIT. THERE ARE TWO 200 AMP SWITCHES WHICH DO NOT HAVE A GROUNDING ELECTRODE CONDUCTOR SYSTEM. ADDITION ILLEGAL WIRING METHODS HAVE BEEN DONE TO MULTIPLE PANELS AT THE MAIN SERVICE LOCATION. THE WOOD FRAMED SUPPORT STRUCTURE TO THE MAIN SERVICE DISCONNECTS IS DETERIORATED AND IS FAILING. |
| 12/16/2014 | INSP - FOLLOW UP CODE ENFORCE | VALDEZ | Approved | MET ON SITE WITH CONTRACTOR ANGEL, WE WALKED THE PARK AND I EXPLAINED THAT A PERMIT IS REQUIRED HE SAID HE WILL PULL A PERMIT WITHIN A FEW DAYS |
Completed Activity Special Conditions
Case Description - WORK WITHOUT PERMITS-COMMERCL
Case Number - T14DV02111
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 8
| Date | Name |
| 04/02/2014 | CONTACTED BY PHONE |
| 04/03/2014 | CONTACTED IN PERSON |
| 04/23/2014 | CONTACTED BY MAILING |
| 06/23/2014 | CONTACTED BY EMAIL |
| 04/03/2014 | NOTICE AND ORDER ISSUED |
| 04/23/2014 | NOTICE OF VIOLATION ISSUED |
| 09/13/2017 | CITATION ISSUED |
| 04/22/2014 | T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe. |