Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T14DV02111
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2014 | INSP - INITIAL CODE ENFORCMENT | Approved | THERE ARE DILAPIDATED SUPPORT POSTS THOUGH OUT THE PARK WHICH HAVE FAILED IN SUPPORTING THE OVERHEAD FEEDERS WHICH ARE CURRENTLY RESTING AND CONTACTING THE EXTERIOR BODY OF THE MOBILES HOMES. THERE ARE NEWLY INSTALL FEEDERS TO MULITPLE UNMARKED LOCATIONS. ALL THIS WORK WAS DONE WITH OUT A PERMIT. THERE ARE TWO 200 AMP SWITCHES WHICH DO NOT HAVE A GROUNDING ELECTRODE CONDUCTOR SYSTEM. ADDITION ILLEGAL WIRING METHODS HAVE BEEN DONE TO MULTIPLE PANELS AT THE MAIN SERVICE LOCATION. THE WOOD FRAMED SUPPORT STRUCTURE TO THE MAIN SERVICE DISCONNECTS IS DETERIORATED AND IS FAILING. |