Case: T10FR02522
Case Details
Entered Date:
11/30/2010
Applicant:
DESERT CHRISTIAN HIGH SCHOOL INC
Description:
Full inspection done 11/29/2010; E occupancy; Ernie Erbe - 603-7462;
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02522
Case Description: INSPECTION
Total Completed Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2010 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Approved | FDC not Visible: 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters "FDC" at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official. ______ Attach approved "FDC" signs [Red on White letters] x3 as we discussed. |
11/30/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Electrical Room Label: 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ______ Place a sign "Electrical Room" and "Enunciator Panel" in 3" Red on White on the Electrical room door, and buildings south side. |
11/30/2010 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Approved | Open wire boxes/ splices: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner. |
11/30/2010 | INSP - FULL | BCOBB | Approved | Please correct the following Tucson Fire Code violations: |