Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T10FR02522
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2011 | VIOL - BUILDING SVCS & SYSTEMS | Approved | ||
11/30/2010 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Open wire boxes/ splices: TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. ______Cover wires in an approved manner. |
|
11/30/2010 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Electrical Room Label: 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ______ Place a sign "Electrical Room" and "Enunciator Panel" in 3" Red on White on the Electrical room door, and buildings south side. |