Case: T10FR02522

Parcel: 13313005F


Addresses:

7525 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR02522

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
01/12/2011 VIOL - BUILDING SVCS & SYSTEMS Approved
11/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire boxes/ splices:

TFC2006 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

______Cover wires in an approved manner.
11/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical Room Label:
605.3.1 Labeling. Doors into electrical control panel rooms
shall be marked with a plainly visible and legible sign stating
ELECTRICAL ROOM or similar approved wording.
The disconnecting means for each service, feeder or branch
circuit originating on a switchboard or panelboard shall be
legibly and durably marked to indicate its purpose unless
such purpose is clearly evident.

______ Place a sign "Electrical Room" and "Enunciator Panel" in 3" Red on White on the Electrical room door, and buildings south side.