Case: T10FR02522

Parcel: 13313005F


Addresses:

7525 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T10FR02522

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
01/12/2011 VIOL - FIRE PROTECTION SYSTEMS Approved All approved - good job!
11/30/2010 VIOL - FIRE PROTECTION SYSTEMS Violation FDC not Visible:
912.2.2 Existing buildings. On existing buildings, wherever
the fire department connection is not visible to
approaching fire apparatus, the fire department connection
shall be indicated by an approved sign mounted on the street
front or on the side of the building. Such sign shall have the
letters "FDC" at least 6 inches (152 mm) high and words in
letters at least 2 inches (51 mm) high or an arrow to indicate
the location. All such signs shall be subject to the approval
of the fire code official.

______ Attach approved "FDC" signs [Red on White letters] x3 as we discussed.