Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T10FR02522
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/12/2011 | VIOL - FIRE PROTECTION SYSTEMS | Approved | All approved - good job! | |
11/30/2010 | VIOL - FIRE PROTECTION SYSTEMS | Violation | FDC not Visible: 912.2.2 Existing buildings. On existing buildings, wherever the fire department connection is not visible to approaching fire apparatus, the fire department connection shall be indicated by an approved sign mounted on the street front or on the side of the building. Such sign shall have the letters "FDC" at least 6 inches (152 mm) high and words in letters at least 2 inches (51 mm) high or an arrow to indicate the location. All such signs shall be subject to the approval of the fire code official. ______ Attach approved "FDC" signs [Red on White letters] x3 as we discussed. |