Case: T10FR02304
Case Details
Entered Date:
11/03/2010
Applicant:
PRINCE & FAIRVIEW PLAZA LLC
Description:
Full Fire Prevention Inspection. Jeremy Dawson-- 293-7339
Outstanding Inspections
Case Number: T10FR02304
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2010 | VIOL - ADMINISTRATION | JBURGE | Correction Required | IFC 111.1 Order. Whenever the fire code official finds any work regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the fire code official is authorized to issue a stop work order. _____1. Cease and desist the use of all cooking equipment located in the kitchen. THE SYSTEM AND EQUIPMENT HAS BEEN RED TAGGED. _____2. The kitchen hood extinguishing system shall be serviced and repaired where defective. |
11/03/2010 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. The electrical panel located in the office shall have approved covers where the electrical breakers have been removed. |
11/03/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag all portable fire extinguishers. _____2. The hood extinguishing system shall be serviced and all deficiencies corrected. |
11/03/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1. Clean and remove all grease accumulation from the Kitchen hood system. NOTE: Provide documentation of the cleaning. |
11/03/2010 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | IFC Section 904.11.7 All deep-fat fryers shall be installed with at least a 16 inch (406 mm) space between the fryer and surface flames of adjacent cooking appliances. Exception: 1. Where a steel or tempered glass baffle plate is installed at a minimum 8 inches (203 mm) in height between the fryer and surface flames of the adjacent cooking appliance, the requirement for a 16 inch space shall not apply. Where the fryer and the surface flames of the adjacent cooking appliance are at different horizontal planes, the minimum height of 8 inches (203 mm) shall be measured from the higher of the two. _____1. The deep fat fryer shall be separated from the open flame gas range and shall meet the separation requirements in this code. |
11/03/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a GroupAor E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. _____1. The Northwest EXIT door shall have panic hardware installed. |
11/03/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the emergency lighting unit located on the East wall by the main entrance. _____2. Repair or replace the emergency lighting unit located on the West wall by the main entrance. _____3. Repair or replace the emergency lighting units located on the wall by the bar door. _____4. Repair or replace the emergency lighting unit located on the wall by the South EXIT door. _____5. Repair or replace the emergency lighting units located on the West wall by the DJ booth. _____6. Repair or replace the emergency lighting unit located on the wall by the northwest EXIT door.. |
11/03/2010 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | IFC Section 1028.8 Panic hardware. Where panic and fire exit hardware is installed, the panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code. _____1. Remove the thumb-turn lock from the Northwest EXIT door. |
11/03/2010 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | IFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. The CO2 cylinders located by the bar shall be secured with a chain or strap to prevent them from falling. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR02304
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/27/2010 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |