Case: T10FR02304

Parcel: 10607001F


Addresses:

915 W PRINCE RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T10FR02304

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
11/03/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1. Repair or replace the emergency lighting unit located on the East wall by the main entrance.

_____2. Repair or replace the emergency lighting unit located on the West wall by the main entrance.

_____3. Repair or replace the emergency lighting units located on the wall by the bar door.

_____4. Repair or replace the emergency lighting unit located on the wall by the South EXIT door.

_____5. Repair or replace the emergency lighting units located on the West wall by the DJ booth.

_____6. Repair or replace the emergency lighting unit located on the wall by the northwest EXIT door..
11/03/2010 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.9 Panic and fire exit hardware. Where panic and
fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall
extend at least one-half of the door leaf width.
2. The maximum unlatching force shall not exceed 15
pounds (67 N).
Each door in a means of egress from a GroupAor E occupancy
having an occupant load of 50 or more and any Group
H occupancy shall not be provided with a latch or lock
unless it is panic hardware or fire exit hardware.

_____1. The Northwest EXIT door shall have panic hardware installed.
11/03/2010 VIOL - MEANS OF EGRESS Correction Required IFC Section 1028.8 Panic hardware. Where panic and fire exit hardware is installed,
the panic or fire exit hardware shall be the only locking device on the door except
where otherwise permitted in this code.

_____1. Remove the thumb-turn lock from the Northwest EXIT door.