Description:

Pinnacle Peak Steak House 4/19/10

Outstanding Inspections

Case Number: T10FR00769
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
04/20/2010 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 609.2 Where required A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. _____Place extinguishing system over gas stove.
04/20/2010 VIOL - INT.FINISH, DEC. MATL'S MPURSLEY Correction Required 807.1.2 General requirements Curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 806.2 or be noncombustible, and must be no more then 10% of total surface area. _____ Remove ties from walls, limiting them only to the rafters with minimum of 24 inches around sprinkler heads. Spray ties with flame retardant as they are hung.
04/21/2010 VIOL - FIRE PROTECTION SYSTEMS MPursley Correction Required 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. _____Move light rail away from sprinkler head
04/21/2010 VIOL - MEANS OF EGRESS MPursley Correction Required 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix, repair, and/or replace the emergency lighting in order to meet code standards 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____ Remove the slide bolt from the dish room egress door, as bolt lock of any kind are not permitted 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). 3. No additional locks or latches shall be added _____Turn tension down on bar door 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00769
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/14/2010 INSP - REINSPECTION MPursley Approved All corrections made 6/11/10