Inspection Status: Correction Required
Inspection History: VIOL - INT.FINISH, DEC. MATL'S
Case Number - T10FR00769
Inspection Description - VIOL - INT.FINISH, DEC. MATL'S
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2010 | VIOL - INT.FINISH, DEC. MATL'S | Correction Required | 807.1.2 General requirements Curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 806.2 or be noncombustible, and must be no more then 10% of total surface area. _____ Remove ties from walls, limiting them only to the rafters with minimum of 24 inches around sprinkler heads. Spray ties with flame retardant as they are hung. |