Case: T10FR00687
Case Details
Entered Date:
04/02/2010
Applicant:
CATALINA POST 4903 VETERANS OF FOREIGN
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T10FR00687
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 10
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2010 | VIOL - FIRE SERVICE FEATURES | WMOTTO | Correction Required | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. 1___ LABLE RISER ROOM ON OUTSIDE OF DOOR. |
| 04/02/2010 | VIOL - FIRE SERVICE FEATURES | WMOTTO | Correction Required | 605.4.1 Power tap design. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed in accordance with UL 1363. 1___ REPLACE MULTIPLUG ADAPTER WITH GFI PROTECTION BEHIND GAMING MACHINES. 2___ REPLACE MULTIPLUG ADAPTER BEHIND COFFEE MACHINE. WITH GFI PROTECTION. 3___ REPLACE MULTIPLUG ADAPTER IN KITCHEN WITH GFI. |
| 04/02/2010 | VIOL - FIRE RESIST.RATED CONST | WMOTTO | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. 1___ FIX CEILING TILE IN BALL ROOM. 2___ FIX CEILING TILE IN KAROEKE ROOM. 3___ FIX CEILING TILE IN QUARTER MASTER ROOM. |
| 04/02/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 1___ SPRINKLER SYSTEM NEEDS TO BE SERVICED AND TAGGED ONCE A YEAR. |
| 04/02/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. 1___ KITCHEN HOOD SYSTEM NEEDS TO BE SERVICED AND TAGGED EVERY SIX MONTHS. |
| 04/02/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. 1___ EXTINGUISHERS NEED TO BE SERVICED AND TAGGED. 2___ SERVICE AND TAG CLASS K EXTINGUISHER IN KITCHEN |
| 04/02/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. 1___ REPAIR EMERGENCY LIGHT IN KAREOKE ROOM. |
| 04/02/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1___ REMOVE LATCH LOCK ON MAIN ENTRY DOOR. |
| 04/02/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Correction Required | 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. 1___ REPAIR EXIT SIGN IN KICHEN. 2___ REPAIR EXIT SIGN NEAR LAUNDRY ROOM EXIT DOOR. 3___ REPAIR EXIT SIGN SOUTH EXIT DOOR IN KITCHEN. |
| 04/02/2010 | VIOL - COMPRESSED GASES | WMOTTO | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. 1__ SECURE CO2 BOTTLES TO PREVENT FALLING. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00687
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2010 | INSP - FULL | WMOTTO | Approved | ALL VIOLATIONS ABATED. HAD SPRINKLER INSPECTION DONE. UNITED FIRE REPLACED ALARM VALVE GAUGES BAD PIPES. SPRINKLER SYSTEM IS GOOD NO DEFICIENCIES. |