Case: T10FR00687

Parcel: 12112024E


Addresses:

1150 N BEVERLY AV

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
04/02/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

1___ EXTINGUISHERS NEED TO BE SERVICED AND TAGGED.
2___ SERVICE AND TAG CLASS K EXTINGUISHER IN KITCHEN
04/02/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

1___ KITCHEN HOOD SYSTEM NEEDS TO BE SERVICED AND TAGGED EVERY SIX MONTHS.
04/02/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

1___ SPRINKLER SYSTEM NEEDS TO BE SERVICED AND TAGGED ONCE A YEAR.