Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2010 | VIOL - MEANS OF EGRESS | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1___ REMOVE LATCH LOCK ON MAIN ENTRY DOOR. |
|
| 04/02/2010 | VIOL - MEANS OF EGRESS | Correction Required | 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. 1___ REPAIR EMERGENCY LIGHT IN KAREOKE ROOM. |
|
| 04/02/2010 | VIOL - MEANS OF EGRESS | Correction Required | 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. Decorations, furnishings, equipment or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. 1___ REPAIR EXIT SIGN IN KICHEN. 2___ REPAIR EXIT SIGN NEAR LAUNDRY ROOM EXIT DOOR. 3___ REPAIR EXIT SIGN SOUTH EXIT DOOR IN KITCHEN. |