Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/30/2010

Applicant:

SMITHS FOOD & DRUG CENTERS INC

Description:

902 w irvington FRY's fire inspection.

Outstanding Inspections

Case Number: T10FR00678
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
03/30/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformer.
03/30/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. ***Provide such signage.
03/30/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. __Remove/replace all unprotected extension cords being used as permanent wiring.
03/30/2010 VIOL - BUILDING SVCS & SYSTEMS JLOYA Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
03/30/2010 VIOL - FIRE RESIST.RATED CONST JLOYA Violation 703.1 - The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. ***Replace missing ceiling tiles.
03/30/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 901.6.2 - Records of all system inspections, tests, and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years and made available to the fire code official upon request. ___Provide copy of last sprinkler inspection report.
03/30/2010 VIOL - FIRE PROTECTION SYSTEMS JLOYA Violation 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. ___Front entrance plants area.
03/30/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting
03/30/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ___ Bakery doors
03/30/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs
03/30/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1027.6 Panic Hardware:Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door __ Remove locking mechanism from emergency exit from upstairs.
03/30/2010 VIOL - MEANS OF EGRESS JLOYA Violation 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. __ Maintain exit hallways clear.
03/30/2010 VIOL - MEANS OF EGRESS JLOYA Violation TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building. ____ emergency exit from upstairs office.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00678
Case Description: INSPECTION
Total Completed Inspections - 2
End Date Description Inspector Results Comments
03/30/2010 INSP - FULL JLOYA Approved Correct the following fire code violations found during life/safety fire inspection. Thank you for your cooperation, for any questions please contact inspector Jorge Loya @ 837-7118, Fax 791-5346. Received by_________________ Date__________
04/21/2010 INSP - REINSPECTION JLOYA Approved All violations abated.