Case: T10FR00678

Parcel: 120052720


Addresses:

902 W IRVINGTON RD


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T10FR00678

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
03/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.
_____ Clear area around electrical panels and transformer.
03/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident.
***Provide such signage.
03/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with portable appliances.

__Remove/replace all unprotected extension cords being used as permanent wiring.
03/30/2010 VIOL - BUILDING SVCS & SYSTEMS Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.