Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T10FR00678
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/30/2010 | VIOL - MEANS OF EGRESS | Violation | TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Provide emergency lighting that is activated by loss of power to building. ____ emergency exit from upstairs office. |
|
03/30/2010 | VIOL - MEANS OF EGRESS | Violation | 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. _____ Repair or replace batteries in emergency lighting |
|
03/30/2010 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ___ Bakery doors |
|
03/30/2010 | VIOL - MEANS OF EGRESS | Violation | 1027.6 Panic Hardware:Where panic hardware and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door __ Remove locking mechanism from emergency exit from upstairs. |
|
03/30/2010 | VIOL - MEANS OF EGRESS | Violation | 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace exit signs |
|
03/30/2010 | VIOL - MEANS OF EGRESS | Violation | 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. __ Maintain exit hallways clear. |