Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/23/2010

Applicant:

WASTE MANAGEMENT OF ARIZONA INC

Description:

Full Fire Prevention Inspection. Frank Greaney 292-2900 Cell- 382-7696

Outstanding Inspections

Case Number: T10FR00619
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
03/23/2010 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required IFC 310.3 “No Smoking” signs. The fire code official is authorized to order the posting of “No Smoking” signs in a conspicuous location in each structure or location in which smoking is prohibited. The content, lettering, size, color and location of required “No Smoking” signs shall be approved. _____1. Post " NO SMOKING" signs in the inside shop.
03/23/2010 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required IFC 315.3 Outside storage. Outside storage of combustible materials shall not be located within 10 feet (3048 mm) of a property line. Exceptions: 1. The separation distance is allowed to be reduced to 3 feet (914 mm) for storage not exceeding 6 feet (1829 mm) in height. 2. The separation distance is allowed to be reduced when the fire code official determines that no hazard to the adjoining property exists. _____1. Maintain the storage distance requirements noted in this code. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
03/23/2010 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. _____1. Remove the storage from obstructing the electrical panel.
03/23/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Repair or replace the smoke/heat detector located in the fire control panel room. _____2. Inspect and test all fire hose reels and cabinets.
03/23/2010 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. _____1. Mount the portable fire extinguisher located by the west side back wall.

Completed Inspections

Case Status: COMPLETE
Case Number: T10FR00619
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/12/2010 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.