Case: T10FR00619

Parcel: 103090520


Addresses:

3909 N RUNWAY DR

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
03/23/2010 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.

_____1. Remove the storage from obstructing the electrical panel.