Case: T10FR00619

Parcel: 103090520


Addresses:

3909 N RUNWAY DR

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
03/23/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.

_____1. Repair or replace the smoke/heat detector located in the fire control panel room.

_____2. Inspect and test all fire hose reels and cabinets.
03/23/2010 VIOL - FIRE PROTECTION SYSTEMS Correction Required IFC 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.

_____1. Mount the portable fire extinguisher located by the west side back wall.