Case: T10FR00099
Case Details
Entered Date:
01/19/2010
Applicant:
WEST MAIN GATE CENTER LLC
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T10FR00099
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
VIOL - BUILDING SVCS & SYSTEMS | None | Not Inspected | ||
01/19/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. 1___ NEED TO DROP SPRINKLER HEADS BELOW PALM CANOPY OVER OUTSIDE PATIO BAR UPSTAIRS. 2___ NEED TO HAVE SPRINKLER HEAD IN ROOM OVER MIXER. 3___ NEED SPRINKLER HEAD IN TOOL ROOM. |
01/19/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 904.1 General. Automatic fire-extinguishing systems, other than automatic sprinkler systems, shall be designed, installed, inspected, tested and maintained in accordance with the provisions of this section and the applicable referenced standards. 1___ NEED TO HAVE KITCHEN HOOD SERVICED AND TAGGED. |
01/19/2010 | VIOL - FIRE PROTECTION SYSTEMS | WMOTTO | Correction Required | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. 1___ CLASS K EXTINGUISHER IN KITCHEN NEEDS TO BE SERVICED. |
01/19/2010 | VIOL - COMPRESSED GASES | WMOTTO | Correction Required | 3003.5 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgement and against access by unauthorized personnel in accordance with Sections 3003.5.1 through 3003.5.3. 1___ PROPERLY SECURE GAS CYLINDERS NEAR RISER. |
Completed Inspections
Case Status: COMPLETE
Case Number: T10FR00099
Case Description: INSPECTION
Total Completed Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/31/2010 | VIOL - MEANS OF EGRESS | WMOTTO | Approved | ALL VIOLATIONS ABATED |
08/31/2010 | VIOL - FIRE RESIST.RATED CONST | WMOTTO | Approved | ALL VIOLATIONS ABATED |
08/31/2010 | INSP - FULL | WMOTTO | Approved | ALL VIOLATIONS ABATED. |