Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

12/09/2009

Applicant:

EL CHARRO ENTERPRISES INC

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T09FR03707
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
12/09/2009 INSP - FULL WMOTTO Correction Required PLEASE CORRECT TUCSON FIRE CODE VIOLATIONS.
12/09/2009 VIOL - FIRE SERVICE FEATURES WMOTTO Correction Required IFC 505.1 Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. ___1. SEE ATTACHED DOCUMENT ON ADRESS DISPLAY REQUIREMENTS.
12/09/2009 VIOL - BUILDING SVCS & SYSTEMS WMOTTO Correction Required IFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. ___1. NEED ELECTRICAL OUTLET IN SOUTH KITCHEN NEXT TO FRYER. ___2. NEED ELECTRICAL OUTLET IN OUTSIDE PATIO ACROSS FROM OUSIDE BAR.
12/10/2009 VIOL - FIRE PROTECTION SYSTEMS WMOTTO Correction Required IFC 904.2.1 Commercial hood and duct systems. Each required commercial kitchen exhaust hood and duct system required by Section 610 to have a Type I hood shall be protected with an approved automatic fire-extinguishing system installed in accordance with this code. ___1. OUTSIDE GRILL UNDER CANOPY NEEDS AN EXTINGUISHING SYSTEM WITHIN THE HOOD.
12/10/2009 VIOL - MEANS OF EGRESS WMOTTO Correction Required IFC 1008.1.2 Door swing. Egress doors shall be side-hinged swinging .Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. ___1. OUTSIDE DOOR ON EAST END OF BUILDING LEADING TO OUTSIDE PATIO NEEDS TO SWING OUTWARD.
12/10/2009 VIOL - MEANS OF EGRESS WMOTTO Correction Required IFC TFC 803.1.3 Obstructions. Furnishings or other objects shall not be placed to obstruct exits, access there to, egress there from or visibility thereof. ___1. THE VIRGIN MARY ROOM NEEDS TO BE RECONFIGURED TO ALLOW MORE SPACE AT THE EXIT DOOR.