Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T09FR03707
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/10/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1008.1.2 Door swing. Egress doors shall be side-hinged swinging .Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. ___1. OUTSIDE DOOR ON EAST END OF BUILDING LEADING TO OUTSIDE PATIO NEEDS TO SWING OUTWARD. |
|
12/10/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC TFC 803.1.3 Obstructions. Furnishings or other objects shall not be placed to obstruct exits, access there to, egress there from or visibility thereof. ___1. THE VIRGIN MARY ROOM NEEDS TO BE RECONFIGURED TO ALLOW MORE SPACE AT THE EXIT DOOR. |
|
12/09/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress. ___1. NEED TO HAVE ALL EMERGENCY LIGHTS TESTED WITH BRAKER OFF. REPAIR ANY NOT WORKING. ___2. REPAIR EMERGENCY LIGHT OVER SINK. ___3. REPAIR EMERGENCY LIGHT BY BAR ENTRANCE INSIDE. ___4. REPAIR EMERGENCY LIGHT NEAR EXIT IN BREEZWAY TO BAR. |
|
12/09/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1011.5.1 Graphics. Every exit sign and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with the principal strokes of the letters not less than 0.75 inch (19.1 mm) wide. The word “EXIT” shall have letters having a width not less than 2 inches (51 mm) wide, except the letter “I,” and the minimum spacing between letters shall not be less than 0.375 inch (9.5 mm). Signs larger than the minimum established in this section shall have letter widths, strokes and spacing in proportion to their height. ___1. NEED PROPER EXIT SIGN BY TABLE 16. |
|
12/09/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ___1. EXIT SIGN BULB OUT NORTH EXIT BY BAR. |
|
12/09/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. ___1. MAIN DOOR IN N BUILDING NEEDS SIGN : THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. ___2. E DOOR IN COFFE SHOP NEEDS SIGN THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. |
|
12/09/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). Each door in a means of egress from a GroupAor E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. ___1.NEED PANIC HARDWARE ON EXIT DOORS IN NORTH RESTRAUNT UPSTAIRS EXECEPT MAIN DOOR. ___2. NEED TO REMOVE THUMB TURN LOCK ADD PANIC HARDWARE TO NORTHEST DINNING AREA DOOR LEADING TO INDOOR PATIO. |
|
12/09/2009 | VIOL - MEANS OF EGRESS | Correction Required | IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ___1. SLIDE BOLT NEEDS TO BE REMOVED ON GLASS DOOR IN PATIO NORTH BUILDING LEADING TO PATIO. ___2. SLIDE LOCKS AND LEVER LATCH NEEDS TO BE REMOVED ON DOOR LEADING TO PATIO. |