Case: T09FR03707

Parcel: 117100950


Addresses:

311 N COURT AV


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR03707

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
12/10/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.2 Door swing. Egress doors shall be side-hinged
swinging .Doors shall swing in the direction of egress travel where
serving an occupant load of 50 or more persons or a Group
H occupancy.

___1. OUTSIDE DOOR ON EAST END OF BUILDING LEADING TO OUTSIDE PATIO NEEDS TO SWING OUTWARD.
12/10/2009 VIOL - MEANS OF EGRESS Correction Required IFC TFC 803.1.3 Obstructions. Furnishings or other objects shall not be placed to obstruct exits, access there to, egress there from or visibility thereof.

___1. THE VIRGIN MARY ROOM NEEDS TO BE RECONFIGURED TO ALLOW MORE SPACE AT THE EXIT DOOR.
12/09/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress.

___1. NEED TO HAVE ALL EMERGENCY LIGHTS TESTED WITH BRAKER OFF. REPAIR ANY NOT WORKING.
___2. REPAIR EMERGENCY LIGHT OVER SINK.
___3. REPAIR EMERGENCY LIGHT BY BAR ENTRANCE INSIDE.
___4. REPAIR EMERGENCY LIGHT NEAR EXIT IN BREEZWAY TO BAR.
12/09/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1011.5.1 Graphics. Every exit sign and directional exit sign
shall have plainly legible letters not less than 6 inches (152
mm) high with the principal strokes of the letters not less
than 0.75 inch (19.1 mm) wide. The word “EXIT” shall
have letters having a width not less than 2 inches (51 mm)
wide, except the letter “I,” and the minimum spacing
between letters shall not be less than 0.375 inch (9.5 mm).
Signs larger than the minimum established in this section
shall have letter widths, strokes and spacing in proportion to
their height.

___1. NEED PROPER EXIT SIGN BY TABLE 16.
12/09/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1011.5.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration of
not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator. The installation of the emergency
power system shall be in accordance with Section
2702 of the International Building Code.

___1. EXIT SIGN BULB OUT NORTH EXIT BY BAR.
12/09/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where any of
the following exists:
1. Places of detention or restraint.
2. In buildings in occupancy Group A having an
occupant load of 300 or less, Groups B, F,Mand S,
and in places of religious worship, the main exterior
door or doors are permitted to be equipped
with key-operated locking devices from the egress
side provided:
2.1. The locking device is readily distinguishable
as locked,
2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating. The sign shall be in letters 1
inch (25 mm) high on a contrasting background.

___1. MAIN DOOR IN N BUILDING NEEDS SIGN : THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
___2. E DOOR IN COFFE SHOP NEEDS SIGN THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
12/09/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.9 Panic and fire exit hardware. Where panic and
fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall
extend at least one-half of the door leaf width.
2. The maximum unlatching force shall not exceed 15
pounds (67 N).
Each door in a means of egress from a GroupAor E occupancy
having an occupant load of 50 or more and any Group
H occupancy shall not be provided with a latch or lock
unless it is panic hardware or fire exit hardware.

___1.NEED PANIC HARDWARE ON EXIT DOORS IN NORTH RESTRAUNT UPSTAIRS EXECEPT MAIN DOOR.
___2. NEED TO REMOVE THUMB TURN LOCK ADD PANIC HARDWARE TO NORTHEST DINNING AREA DOOR LEADING TO INDOOR PATIO.
12/09/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

___1. SLIDE BOLT NEEDS TO BE REMOVED ON GLASS DOOR IN PATIO NORTH BUILDING LEADING TO PATIO.
___2. SLIDE LOCKS AND LEVER LATCH NEEDS TO BE REMOVED ON DOOR LEADING TO PATIO.