Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/10/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 904.2.1 Commercial hood and duct systems. Each required commercial kitchen exhaust hood and duct system required by Section 610 to have a Type I hood shall be protected with an approved automatic fire-extinguishing system installed in accordance with this code. ___1. OUTSIDE GRILL UNDER CANOPY NEEDS AN EXTINGUISHING SYSTEM WITHIN THE HOOD. |
|
| 12/09/2009 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ___1. NEED TO SHOW REPORT HOOD HAS BEEN SERVICED REPAIR ANY DEFECENCIES ON REPORT. ___2. NOZZLES NEED TO BE ADJUSTED FOR PROPER COVERAGE. ___3. APPLIANCE IN NORTH KITCHEN HANGING OUTSIDE OF EAST END OF HOOD SYSTEM. ___4. APPLIANCES NOT UNDER HOOD BOTH ENDS OF HOOD SYSTEM IN NORTH KITCHEN. |