Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/25/2009

Applicant:

65-75 E PENNINGTON LLC

Description:

Full Fire Prevention Inspection. Paul Leschak 622-1000

Outstanding Inspections

Case Number: T09FR03118
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
09/25/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove the cube adapter that powers the radio and coffee maker. NOTE: plug the radio and coffee maker directly into the outlet.
09/25/2009 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required IFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. The light switch located by the door in the kitchen shall have an approved cover.
09/25/2009 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service and tag the CLASS K portable fire extinguisher located in the kitchen. _____2. Service the kitchen hood extinguishing system or upgrade to the UL 300 extinguishing system. _____3. The hood extinguishing system nozzles shall be aligned to properly cover the cooking equipment. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
09/25/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause. _____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" on the inside of the south entrance door.
09/25/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair or replace the emergency lighting lamps loacted above the northeast door.
09/25/2009 VIOL - MEANS OF EGRESS JBURGE Correction Required IFC 1027.8 Opening force for doors. The opening force for interior side-swinging doors without closers shall not exceed a 5-pound (22 N) force. For other side-swinging, sliding and folding doors, the door latch shall release when subjected to a force of not more than 15 pounds (66 N). The door shall be set in motion when subjected to a force not exceeding a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a force of not more than 50 pounds (222 N). Forces shall be applied to the latch side. _____1. The northeast door shall be repaired and open easily.

Completed Inspections

Case Status: COMPLETE
Case Number: T09FR03118
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/25/2009 INSP - FULL JBURGE Approved Please correct all noted Tucson Fire Code violations.