Case: T09FR03118

Parcel: 11711085A


Addresses:

75 E PENNINGTON ST


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR03118

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
09/25/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1027.8 Opening force for doors. The opening force for interior
side-swinging doors without closers shall not exceed a
5-pound (22 N) force. For other side-swinging, sliding and
folding doors, the door latch shall release when subjected to a
force of not more than 15 pounds (66 N). The door shall be set
in motion when subjected to a force not exceeding a 30-pound
(133 N) force. The door shall swing to a full-open position
when subjected to a force of not more than 50 pounds (222 N).
Forces shall be applied to the latch side.

_____1. The northeast door shall be repaired and open easily.
09/25/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system.

_____1. Repair or replace the emergency lighting lamps loacted above the northeast door.
09/25/2009 VIOL - MEANS OF EGRESS Correction Required IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists:
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 2.3. The use of the key-operated locking device is revocable by the fire code official for due cause.

_____1. Post the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" on the inside of the south entrance door.