Case: T09FR02486
Case Details
Entered Date:
07/28/2009
Applicant:
BROADWAY STAR PARTNERS LLC
Description:
Full inspection done 7/28/09; "M" occupancy; C of O on premises; Curt Cornett and Kathy Marquard - business owners 296-5702
Outstanding Inspections
Case Number: T09FR02486
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 14
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/28/2009 | INSP - FULL | BCOBB | Violation | Please correct the following Tucson Fire Code violations: Notes: 1.C of O to be provided upon re-inspection, if available. If not available, manager will be in the process of acquiring it. Certificate of Occupancy [C of O]: 1997 Uniform Administrative Code Section 309.5 Posting. The certificate of occupancy shall be posted in a conspicuous place on the premises and shall not be removed except by the building official. ______ Acquire a C of O from Developmental Services. [791-5550] __XX____ C of O on site. 2. A record of the sprinkler system inspections shall be made available upon re-inspection. |
07/28/2009 | VIOL - PRECAUTION AGAINST FIRE | BCOBB | Violation | Clearance below sprinklers: TFC 315.2.1 Ceiling clearance. Storage shall be maintained 24 inches (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. ______Remove storage to 18 inches or more below sprinkler head. |
07/28/2009 | VIOL - PRECAUTION AGAINST FIRE | BCOBB | Violation | Housekeeping: TFC 304.1 Waste accumulation prohibited. Combustible waste material creating a fire hazard shall not be allowed to accumulate in buildings or structures or upon premises. ______ Clean out closet in back of store, and general area too. |
07/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ______Clear area in front of electrical panel in an approved manner. |
07/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Bulbs against material decorations: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ______ Remove lights from decorations. |
07/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Electrical wires extending through ceiling: TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors. ______ Please remove wires. |
07/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | BCOBB | Violation | Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____Replace with approved fused power strip. [green one in front and all others...orange in back] |
07/28/2009 | VIOL - FIRE RESIST.RATED CONST | BCOBB | Violation | Missing or moved ceiling tiles: TFC2006/ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings, and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. _____Replace missing ceiling tiles. |
07/28/2009 | VIOL - FIRE PROTECTION SYSTEMS | BCOBB | Violation | Escutcheons: [collar around sprinkler head] 903.3.1 Standards. Sprinkler systems shall be designed and installed in accordance with Sections 903.3.1.1, 903.3.1.2 or 903.3.1.3. ______ Repair or replace above item as necessary. Re-inspection date scheduled on or after August 14th, 2009. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department __________________________ - I have received a copy of this inspection report. Building Representative Re-inspection approved: ___________________________ |
07/28/2009 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Blocked exit: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. _______Clear exit area, and maintain it this way. |
07/28/2009 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Dead bolt on lower back door: 1008.1.8.5 Unlatching. The unlatching of any leaf shall not require more than one operation. ______ Remove lowest dead bolt on back door. |
07/28/2009 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Emergency lighting: IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located] ______Fix all inoperative emergency lights. |
07/28/2009 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Exit sign not lit: TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. _____Fix light in exit sign. |
07/28/2009 | VIOL - MEANS OF EGRESS | BCOBB | Violation | Sticky panic hardware on back door: 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. A maximum unlatching force of 15 pounds (67 N). ______ Fix latch in an approved mannor. |