Case: T09FR02486

Parcel: 13323110C


Addresses:

7543 E BROADWAY BL


Inspection Status: Violation

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR02486

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Violation

Date Description Inspector Results Comments
07/28/2009 VIOL - MEANS OF EGRESS Violation Blocked exit:
1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in
this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.

_______Clear exit area, and maintain it this way.
07/28/2009 VIOL - MEANS OF EGRESS Violation Dead bolt on lower back door:
1008.1.8.5 Unlatching. The unlatching of any leaf shall not require more than one operation.

______ Remove lowest dead bolt on back door.
07/28/2009 VIOL - MEANS OF EGRESS Violation Sticky panic hardware on back door:
1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width.
2. A maximum unlatching force of 15 pounds (67 N).

______ Fix latch in an approved mannor.
07/28/2009 VIOL - MEANS OF EGRESS Violation Exit sign not lit:
TFC 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated.
_____Fix light in exit sign.
07/28/2009 VIOL - MEANS OF EGRESS Violation Emergency lighting:
IFC2006 [with modifications]/ 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: [where currently located]

______Fix all inoperative emergency lights.