Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T09FR02486
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Electrical wires extending through ceiling: TFC2006/ 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors. ______ Please remove wires. |
|
| 07/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Extension cords: TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____Replace with approved fused power strip. [green one in front and all others...orange in back] |
|
| 07/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Bulbs against material decorations: TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. ______ Remove lights from decorations. |
|
| 07/28/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | Blocked electrical panel: TFC 605.3 Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. ______Clear area in front of electrical panel in an approved manner. |