Case: T09FR01871
Case Details
Entered Date:
06/04/2009
Applicant:
WILMOT PLAZA LC
Description:
T.J. Maxx Shawna Goodwin 520-721-2081 Inspector M. Pursley *** two addresses: 6337, 6343 ***
Outstanding Inspections
Case Number: T09FR01871
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2009 | INSP - FULL | MPURSLEY | Correction Required | |
06/04/2009 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Maintain proper working space around all electrical panels according to code. 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panel board shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. _____Label door to electrical room. 605.4.3 Installation. Relocatable power tap cords shall not extend through walls, ceilings, floors, under doors or floor coverings, or be subject to environmental or physical damage. ____Place protection over power cord. |
06/04/2009 | VIOL - FIRE RESIST.RATED CONST | MPURSLEY | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile |
06/04/2009 | VIOL - FIRE PROTECTION SYSTEMS | MPURSLEY | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Have sprinkler system tested and tagged |
06/04/2009 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply, in the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ____Have emergency lighting tested. 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code ____Have all exit signs tested/repaired. 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: _____________________ ___/___/___ |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01871
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2009 | INSP - REINSPECTION | MPURSLEY | Approved |