Case: T09FR01871

Parcel: 13321074A


Addresses:

6343 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T09FR01871

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/04/2009 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3 Working space and clearance
A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space.

_____ Maintain proper working space around all electrical panels according to code.

605.3.1 Labeling.
Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. The disconnecting means for each service, feeder or branch circuit originating on a switchboard or panel board shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident.

_____Label door to electrical room.


605.4.3 Installation. Relocatable power tap cords shall not
extend through walls, ceilings, floors, under doors or floor
coverings, or be subject to environmental or physical damage.

____Place protection over power cord.