Case: T09FR01871

Parcel: 13321074A


Addresses:

6343 E BROADWAY BL


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T09FR01871

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/04/2009 VIOL - MEANS OF EGRESS Correction Required 1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises' electrical supply, in the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code.

____Have emergency lighting tested.


1011.5.3 Power source.
Exit signs shall be illuminated at all times. To ensure continued illumination for the duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code

____Have all exit signs tested/repaired.


1028.2 Reliability.
Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied.

1028.3 Obstructions.
A means of egress shall be free from obstructions that would prevent its use.

_____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your


Call Inspector Pursley at 235-4709 or 791-4502, if you have any further questions.
Thank you.

Re-inspection passed: _____________________ ___/___/___