Case Details

Status:

FIELD

Type:

COMPLAINT (COMMERCIAL)

Entered Date:

05/14/2009

Applicant:

RANCHO CENTER LLC

Description:

SPRINKLER COMPLAINT

Outstanding Inspections

Case Number: T09FR01695
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
05/14/2009 INSP - FULL EDESCHAI Correction Required DURING THE LAST FIRE PROTECTION INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) SUITE # 118 - STORAGE IN THE BACK ROOM SHALL BE MAINTAINED AT LEAST 18" BELOW SPRINKLER DEFLECTORS 2) SUITE # 204 - SPRINKLER COVERAGE SHALL BE ADDED TO THE STORAGE CLOSET 3) SUITE # 114 - A HALL WAY HAS A SPRINKLER HEAD 15' FROM A WALL, THIS EXCEEDS THE ALLOWABLE DISTANCE 4) SUITE # 110 - A SPRINKLER HEAD IS LOCATED 13' FROM THE SOUTHWEST WALL. THIS ALSO EXCEEDS THE ALLOWABLE DISTANCE 5) THE CONTRACTOR SHALL HAVE ACCESS TO SUITES # 120, 200 AND 206 FOR INSPECTION. AND DEFICIENCIES SHALL BE RECORDED FOR THIS OFFICE