Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Case: T09FR01695

Parcel: 125121110


Addresses:

3400 E SPEEDWAY BL

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
05/14/2009 INSP - FULL Correction Required DURING THE LAST FIRE PROTECTION INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) SUITE # 118 - STORAGE IN THE BACK ROOM SHALL BE MAINTAINED AT LEAST 18" BELOW SPRINKLER DEFLECTORS

2) SUITE # 204 - SPRINKLER COVERAGE SHALL BE ADDED TO THE STORAGE CLOSET

3) SUITE # 114 - A HALL WAY HAS A SPRINKLER HEAD 15' FROM A WALL, THIS EXCEEDS THE ALLOWABLE DISTANCE

4) SUITE # 110 - A SPRINKLER HEAD IS LOCATED 13' FROM THE SOUTHWEST WALL. THIS ALSO EXCEEDS THE ALLOWABLE DISTANCE

5) THE CONTRACTOR SHALL HAVE ACCESS TO SUITES # 120, 200 AND 206 FOR INSPECTION. AND DEFICIENCIES SHALL BE RECORDED FOR THIS OFFICE