Case: T09FR01695

Parcel: 125121110


Addresses:

3400 E SPEEDWAY BL


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T09FR01695

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
05/14/2009 INSP - FULL Correction Required DURING THE LAST FIRE PROTECTION INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) SUITE # 118 - STORAGE IN THE BACK ROOM SHALL BE MAINTAINED AT LEAST 18" BELOW SPRINKLER DEFLECTORS

2) SUITE # 204 - SPRINKLER COVERAGE SHALL BE ADDED TO THE STORAGE CLOSET

3) SUITE # 114 - A HALL WAY HAS A SPRINKLER HEAD 15' FROM A WALL, THIS EXCEEDS THE ALLOWABLE DISTANCE

4) SUITE # 110 - A SPRINKLER HEAD IS LOCATED 13' FROM THE SOUTHWEST WALL. THIS ALSO EXCEEDS THE ALLOWABLE DISTANCE

5) THE CONTRACTOR SHALL HAVE ACCESS TO SUITES # 120, 200 AND 206 FOR INSPECTION. AND DEFICIENCIES SHALL BE RECORDED FOR THIS OFFICE