Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T09FR01695
Inspection Description - INSP - FULL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/14/2009 | INSP - FULL | Correction Required | DURING THE LAST FIRE PROTECTION INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) SUITE # 118 - STORAGE IN THE BACK ROOM SHALL BE MAINTAINED AT LEAST 18" BELOW SPRINKLER DEFLECTORS 2) SUITE # 204 - SPRINKLER COVERAGE SHALL BE ADDED TO THE STORAGE CLOSET 3) SUITE # 114 - A HALL WAY HAS A SPRINKLER HEAD 15' FROM A WALL, THIS EXCEEDS THE ALLOWABLE DISTANCE 4) SUITE # 110 - A SPRINKLER HEAD IS LOCATED 13' FROM THE SOUTHWEST WALL. THIS ALSO EXCEEDS THE ALLOWABLE DISTANCE 5) THE CONTRACTOR SHALL HAVE ACCESS TO SUITES # 120, 200 AND 206 FOR INSPECTION. AND DEFICIENCIES SHALL BE RECORDED FOR THIS OFFICE |