Case: T09FR01128
Case Details
Entered Date:
04/02/2009
Applicant:
CRAYCROFT AUTO REPAIR LTD
Description:
Full Inspection conducted 04/01/09 I have received a copy of this report and understand the corrections needed: ________________ Business Representative: Craig Civitella Inspector: __________________, Captain: _____________ David Greenleaf, MA 23 If you have any questions please call 791-4502. Re-inspection: 4/15/09 (or after). Approved ________
Outstanding Inspections
Case Number: T09FR01128
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 12
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| VIOL - FLAMMABLE LIQUIDS | None | Not Inspected | ||
| 04/01/2009 | VIOL - ADMINISTRATION | DGREENLE | Violation | 105.6.16 - Flammable and combustible liquids. An operational permit is required: 3. To store, handle or use Class II or Class IIIA liquids in excess of 25 gallons in a building or in excess of 60 gallons outside a building... _____ Obtain permits for all above-ground storage tanks (AST)'s or remove in accordance with this code. |
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____ Repair welder electric outlet, bay 3 _____ Reaffix electrical box and conduit in Back Bay to wall |
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove multi-plug adaptor (Bay 3/So. wall) near heater. |
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.5 - ... ... flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. _____ Remove flexible cord from doorway in rear of shop. |
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.5.3 - Maintenance. Extension cords shall be maintained in good condition without splices, deterioration or damage. _____ Repair or replace extension cord in the back bay. |
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | TFC 605.6 - Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Provide covers for Junction boxes: _____ Bay 3 ceiling, _____ Bay 3/E. wall, _____ bay |
| 04/01/2009 | VIOL - MOTOR FUEL DISPENSING | DGREENLE | Violation | TFC 2211.6 - Fire extinguishers. Fire extinguishers shall be provided in accordance with Section 906. |
| 04/01/2009 | VIOL - WELDING & OTHER HOT WRK | DGREENLE | Violation | TFC 2604.2.6 - Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum 2-A:20-B:C rating shall be readily accessible within 30 feet (9144 mm) of the location where hot work is performed. _____ Provide extinguishers in areas that welding is performed. |
| 04/02/2009 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Violation | Chapter 906, Portable Fire Extinguishers TFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. (Professional maintenance yearly, manual inspection monthly, affix a tag to the extinguisher with records of these activities.) _____ Have all extinguishers professionally maintained and manually inspected every 30 days thereafter with records of these activities indicated on an affixed tag. TFC 906.3 - Size and distribution. ...Fire extinguishers for occupancies involving flammable or combustible liquids with depths of less than or equal to 0.25-inch shall be selected and placed in accordance with Table 906.3(2)*. Fire extinguishers for occupancies involving flammable or combustible liquids with a depth of greater than 0.25-inch or involving combustible metals shall be selected and placed in accordance with NFPA 10**. * Ordinary Hazard = 10B >30' (or 20B >50') ** Chapter 6.3.2.3 - For flammable liquids hazards of appreciable depth, a Class B fire extinguisher shall be provided on the basis of at least 2 numerical units of Class B extinguishing potential per ft2 of flammable liquid surface of the largest hazard area. 6.3.2.7 - Travel distances for portable fire extinguishers shall not exceed 50 ft. 6.3.2.7.1 - Scattered or widely separated hazards shall be individually protected. TFC 906.5 - Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. TFC 906.7 - Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. TFC 906.9 - Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 shall be installed so that its top is not more than 5 feet above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds shall be installed so that its top is not more than 3.5 feet above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches. _____ Provide and mount extinguishers in an approved manner |
| 04/02/2009 | VIOL - HAZARDOUS MATERIALS,GEN | DGREENLE | Violation | TFC 2703.4 - Material Safety Data Sheets. Material Safety Data Sheets (MSDS) shall be readily available on the premises for hazardous materials... _____ Provide MSDS for all hazardous materials. These can be obtained from (and must be provided by) the vendor of said materials. |
| 04/02/2009 | VIOL - HAZARDOUS MATERIALS,GEN | DGREENLE | Violation | TFC 2703.5.1 - Markings. Individual containers, cartons or packages shall be conspicuously marked or labeled in an approved manner. _____ label used oil containers _____ label parts cleaner |
Completed Inspections
Case Status: COMPLETE
Case Number: T09FR01128
Case Description: INSPECTION
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2009 | INSP - FULL | DGREENLE | Approved | Certificate of Occupancy: ON FILE & POSTED PrFF R. Felix observing |
| 07/21/2009 | INSP - REINSPECTION | DGREENLE | Approved |