Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____ Repair welder electric outlet, bay 3 _____ Reaffix electrical box and conduit in Back Bay to wall |
|
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove multi-plug adaptor (Bay 3/So. wall) near heater. |
|
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6 - Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. Provide covers for Junction boxes: _____ Bay 3 ceiling, _____ Bay 3/E. wall, _____ bay |
|
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5 - ... ... flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. _____ Remove flexible cord from doorway in rear of shop. |
|
| 04/01/2009 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5.3 - Maintenance. Extension cords shall be maintained in good condition without splices, deterioration or damage. _____ Repair or replace extension cord in the back bay. |